RF-AKK2UP.01 KNX RF+ radio switching actuator 2x/230V/10A
Type: MDT RF-AKK2UP.01 KNX RF+ radio switching actuator 2x/230V/10A
EAN: 4251916148522
Bus System: KNX (RF)
Degree of protection: IP20
Installation: Recessed
This MDT KNX RF + radio switching actuator can switch 2 independent electrical loads. and receive KNX-EIB telegrams. The outputs are switched via a monostable relay and can be individually programmed using ETS. You can choose between interlocking functions, status feedback, central switching functions and complex timing functions such as on/off delay and staircase lighting functions. Scene functions are also available. This switching actuator works in the bidirectional mode of the KNX RF + system and can be perfectly installed in existing installations without a KNX bus cable. The MDT KNX RF+ wireless line coupler (RF-LK001.02) is used to connect to the KNX bus. If the mains voltage fails, all outputs are switched off and the status is restored when the mains voltage is restored. You need ETS for commissioning and programming.
Details:
- New KNX RF+ protocol in system mode
- Commissioning with ETS 5
- Normally open and normally closed operation
- Time functions (on/off delay, staircase lighting function)
- Feedback function (active/passive) for all channels
- Logical links
- 8 scenes per channel
- Central functions and blocking of objects for forced operation
- Configurable behavior in case of bus voltage failure/restoration
- Installation in a switch box
- Connection via radio coupler MDT KNX RF+ (RF-LK001.02)
- For modernization without laying bus cables
Number of outputs: 2
Transmission frequency: 868.3 MHz (for operation within the EU)
Range in open space: 150 m
Output level: 10dBm
Sensitivity: >-105dBm
Compatibility: KNX RF S-Mode (with ETS5 support)
Maximum switching capacity
Resistive load: 10A
Capacitive load: 14uF
Voltage: 230VAC
Maximum inrush current: 80A/150µs, 40A/600µs
Maximum load
Bulbs: 1900 W
HV halogen lamps: 800 W
LV halogen lamps: 500 W
Uncompensated fluorescent lamps: 500 W
Parallel compensated fluorescent lamps: 90 W
Maximum number of electronic ballasts: 2
Mechanical switching frequency: 1,000,000
Protection: 10A
Available KNX databases: ETS 5
Supply voltage: 230 V AC / 50 Hz
Mains power 230 V AC: <0.3 W
Ambient temperature: 0 degrees Celsius to +45 degrees Celsius
The maximum transmission distance is 150 m at the test site under the open sky.The range of radio signals in buildings is often stated to be 30 m. But due to the normal absorption of radio signals in buildings, the real distance is:
➢ About 30 m with good requirements: Large free space, good installation position
transmitter and almost no sources of interference in the radio transmission channel, e.g. large conference room.
➢ Reliability of planning:
approx. 20m with people in the room and transmission through some plasterboard walls or up to 2 stone walls, approx. 10m in narrow corridors
➢ The vertical transition of the ceilings must be ensured in any case
Reduction of material extent compared to free space:
Wooden wall, sheet metal wall, glass (without metals) 0-10%
Stone wall, pressed board wall (chipboard) 5-35%
Cement with iron reinforcement 10-90%
Metal, Aluminum (Floor heating) almost a complete barrier
Odhadovaná doba doručenia: 6 - 10 dní