AIO-0410V.01 KNX Analog module
Type: MDT AIO-0410V.01 KNX Analog module 4-fold
EAN: 4251916130015
Bus System: KNX (TP)
Degree of protection: IP20
Construction: DIN sheets
The MDT analog input / output is suitable for controlling devices with 0-10V inputs and for obtaining measured data 0-20 mA / 0-10 V. All channels are galvanically separated from the KNX bus and can be independently configured as input or output.
The input voltage range is 0-10 V or 2-10 V, the inputs can also be operated as a current loop with 0-20 mA or 4-20 mA. Each input can be individually configured using ETS. Min / max, threshold and traffic light functions are available, it is possible to parameterize the conversion of measuring units and DPT. Dinterrupted driver detection.
The output voltage is 0-10 V and can be controlled via 1 byte, 2 byte or 1 bit objects. In the event of a control value failure, emergency operation is automatically activated. Each output has a day / night function to limit the control value.
You need ETS to commission and configure the MDT analog input / output.
- Inputs / outputs galvanically interconnected
- No external power supply required
- Emergency operation in case of setpoint failure
- Faster application downloads (Long frame support for ETS5)
- Integrated bus clutch
- Number of entries: 4
Inputs:
- Input voltage: 0-10V 2-10V
- Internal resistance: 130 kΩ
- Current loop range: 0-20mA 4-20mA
- Max resistance (load): 266Ω
Outputs:
- Output voltage: 0-10V
- Output current max .: 2mA
- Load resistance min .: 5 kΩ
KNX interface specification: TP-256
Available KNX databases: ETS 4/5
Maximum cable cross section:
- KNX bus terminal: 0.8 mm Ø, solid conductor
Supply voltage: KNX bus
KNX bus power consumption: <0,3 W
Ambient temperature: 0 degrees Celsius to +45 degrees Celsius